Check Light
LM-64   Photometric Comparator
Beta Version     1.02b
Testing Luminaire ( File Name: left blank ) to LM-64 / RP-20 parking lighting standard

Manufact: Cat. Number: (left blank)
Filename:(left blank) Test Report: (left blank)
Lumens: Relative Photometry   3360.0 Watts: 50.0
General: Horiz: 360°    Vert: 180° Luminaire Efficacy:  67.2 Lm/W
  The following information is derived from settings and the IES file entered on Page 1.  Settings have ± 2% thresholds.


 Table shows results for filename:   (left blank)  as a parking garage luminaire with 8 ft mounting.

- - - -  Horizontal° - - - -
 
 22.5° 45° 67.5° 90° 112.5° 135° 157.5° 180° 202.5° 225° 247.5° 270° 292.5° 315° 337.5° 360°  
Vertical Candela for wall and ceiling illumination 
180°  0.00.00.00.00.00.00.00.00.00.00.00.00.00.00.00.0 
135°  0.01.610.463.962.18.20.00.00.01.610.063.362.98.60.00.0 
90°  3.77.318.0109.3106.514.36.03.03.56.717.5108.3108.015.06.53.7 
85°  4.016.373.5444.3433.059.06.53.34.015.771.5440.7438.561.06.54.0 
  Vertical FC  60" above floor, radius-feet from light (symmetrical)Horiz
Radius
85°  0.000.010.060.370.360.050.010.000.000.010.060.370.370.050.010.0034 ft
80°  0.050.140.492.962.880.400.090.050.060.140.482.932.920.410.090.0517 ft
75°  0.240.984.2925.8225.193.470.390.220.260.934.1925.6125.523.560.410.2411 ft
70°  0.641.776.3638.1837.325.181.040.620.711.716.2537.9237.705.291.070.648 ft
  Vertical FC  60" above floor, for rectangular layout.Horiz
Dist.
85°  0.000.000.050.370.360.040.000.000.000.000.050.370.370.040.000.0034 ft
80°  0.000.050.392.962.880.310.030.000.000.050.382.932.920.320.030.0017 ft
75°  0.010.343.3825.8225.192.740.140.010.010.333.3125.6125.522.810.140.0111 ft
70°  0.040.625.0138.1837.324.090.370.030.040.614.9337.9237.704.170.380.048 ft
 Horizontal FC on floor, radius-feet from light @  8-ft heightHoriz
Radius
80°  0.000.000.010.070.070.010.000.000.000.000.010.070.070.010.000.0045 ft
75°  0.010.040.160.970.950.130.010.010.010.040.160.960.960.130.020.0130 ft
70°  0.030.090.331.951.910.270.050.030.040.090.321.941.930.270.060.0322 ft
65°  0.070.170.523.143.080.430.120.070.080.160.523.123.100.440.120.0717 ft
60°  0.420.851.241.871.811.130.770.400.470.831.221.861.821.150.790.4214 ft
55°  0.661.281.802.712.621.661.190.640.751.261.782.702.631.671.210.6611 ft
45°  1.121.952.483.683.572.351.881.101.261.942.493.683.572.351.891.128 ft
20°  2.463.273.474.324.263.413.272.462.673.273.484.324.253.403.272.463 ft
 Aisle  Parking Stalls  Drive Aisle Parking Stalls  Drive 
 Min.  = 0.12 fc   Max.  = 4.32 fc  (both underlined)   Max/Min uniformity ratio = 36.00:1 
Red indicates illuminance is outside of IESNA LM-64-01 / RP-20 criteria
Blue > 1/2 min. illuminance can be raised to standard with a like fixture overlapping that coverage line
 Highlighted Blue  Horiz Radius indicates where additional luminaires may be required to meet min. illuminance

Results:
Type:  Asymmetrical Parking Garage
  Side vertical illuminance at  11.0 feet limits mounting distance to 22 ft. centers in drive aisle.

Results are based on illumination requirements of the Lighting Standard.  Garage lighting is based on illuminance criteria for parking module dimensions and for single or double row layout.  Refer to tables for random placement of fixtures and varying dimensions.

 Notes
  • Illuminance results are without the benefit of floor, wall or ceiling reflectance values.
    Wall reflectance may improve floor illuminance only along those borders.
  • The results can suggest maximum spacing of like luminaires required to meet prescribed illumination levels, from which a total count per area may be derived
  • Glare usually results when the luminaire has a significant output level at an angle greater than 70° from the vertical axis.
  • Illuminance is additive. Adjacent luminaire coverage may be overlapped to raise readings up to standard, e.g. if blue print begins at 15-ft, another like luminaire mounted on 30-ft centers with its same side overlapping that same line would double that reading
  • Type-I luminaires have lobes at 0° & 180° OR 90° & 270°. Type-V may have those 4 lobes or have none at all
  • RP-20 minimum illuminance requirements as follows:
    Parking Garage:  1 horizontal FC, 0.5 vertical FC @ 60" up.   Parking Lot:  0.2 horizontal FC, 0.1 vertical FC @ 60" up
  • Use "Horiz Radius" to determine where floor and vertical illuminance criteria meet with least amount of red
  • The IESNA Security Lighting Committee recommends that for facial identification, the minumum vertical illuminance should be 0.5 fc
  • The IESNA recommends that vertical illuminance should be at least 1/2 the horizontal illuminance at the lowest unshadowed point between luminaires


This service provides a quick, simple assessment of lighting comparison to ascertain minimum
wattage and luminaire count. The intended purpose is improved data for calculation of ROI and payback.
Seek a thorough lighting layout by a professional before committing a lighting project.

 © 2011 Patrick Mullins, all rights reserved